NASA-LLIS-0443

Lessons Learned - High Voltage Electric Circuits

active, Most Current
Organization: NASA
Publication Date: 16 November 1992
Status: active
Page Count: 2
scope:

Description of Driving Event:

During the removal of power to a transformer prior to it being serviced, an accidental 2400 Volt line to ground short circuit was created resulting in minor injury to a technician and minor hardware damage. The major contributing factor to this mishap was the use of a drawing that was not adequately checked after additions and changes had been made to the system. The secondary factor was that the technician did not test the voltage on the line side of the potential transformer compartment to verify that the bus was in fact de-energized.

Document History

NASA-LLIS-0443
November 16, 1992
Lessons Learned - High Voltage Electric Circuits
Description of Driving Event: During the removal of power to a transformer prior to it being serviced, an accidental 2400 Volt line to ground short circuit was created resulting in minor injury to a...