NASA-LLIS-1096

Lessons Learned – Construction Site Safety/Handling Pressurized Pipes/Compressed Air Line

active, Most Current
Organization: NASA
Publication Date: 28 August 1997
Status: active
Page Count: 3
scope:

Description of Driving Event:

On 8/28/97, the last working day before Labor Day weekend, a Contractor's was installing a 3" copper underground compressed air line into a trench approximately 18" wide and 3 feet deep. After having completed about 100 feet of pipe, the Contractor's crew began a pressure test of the 3" pipeline for acceptance. The test was performed prior to installation of a secondary fiberglass pipe to cover the 3" copper pipe and backfill the trench. The specified working pressure of the 3" copper compressed air line was 125 PSI. The specified test pressure was 188 PSI. While the 3" copper line was still under pressure test, the crew began to install the secondary fiberglass pipe to encase the 3" copper primary pipe. As the crew was lowering the pipe into the trench, approximately 2:45 PM, the crew heard the sound of a "pop" and then the sound of leaking air coming from a pipe joint coupling. While the 3" copper line was still under pressure, one worker went into the trench attempting to check the location and the extent of the leak. While the worker was checking the position and direction of the leak from the pipe coupling, the soldered joint failed and the pipeline de-pressurized explosively. An 84-foot section of the pipeline that lead from the bottom of the trench to ground level was propelled approximately 8 to 9 feet longitudinally along the edge of the trench. Air from the explosive depressurization blew sand and soil on the worker in the trench. The sand abraded the worker's arms, chest, and abdominal. The pipe also struck the worker in the left knee and groin area. The worker was taken to the Edwards AFB Hospital for treatment. The worker was released from the hospital after treatment that evening. The worker was wearing personal protective equipment (PPE) including a hardhat, boots, safety glasses, and gloves at the time of the accident.

Document History

NASA-LLIS-1096
August 28, 1997
Lessons Learned – Construction Site Safety/Handling Pressurized Pipes/Compressed Air Line
Description of Driving Event: On 8/28/97, the last working day before Labor Day weekend, a Contractor's was installing a 3" copper underground compressed air line into a trench approximately 18"...