NASA-LLIS-2876

Lessons Learned - Battery Explosion

active, Most Current
Organization: NASA
Publication Date: 18 October 2010
Status: active
Page Count: 2
scope:

Abstract:

A lead acid battery used for emergency generator starting burst and spread surfuric acid within close proximity of the generator. Diesel Generators (stand-by use) are located in a room at the facility that must be accessed by personnel for reasons other than maintenance. Personnel cannot be expected to recognize the presence and potential hazards of dangerous battery failures at undetermined times. Preventative maintenance schedules will include increased checks and ensure appropriate barriers are purchased and/or constructed to prevent personnel exposure to battery faults for all generators.

Document History

NASA-LLIS-2876
October 18, 2010
Lessons Learned - Battery Explosion
Abstract: A lead acid battery used for emergency generator starting burst and spread surfuric acid within close proximity of the generator. Diesel Generators (stand-by use) are located in a room at...