ULSE - UL 1363
Relocatable Power Taps
| Organization: | ULSE |
| Publication Date: | 13 July 2023 |
| Status: | active |
scope:
1.1 These requirements cover indoor use cord and plug connected, relocatable power taps (RPT) rated 250 V AC or less and 20 Amperes or less. A RPT may include an integral Class 2 power supply with an integral lead and/or connector(s) output. In accordance with the National Electric Code, NFPA 70, RPT are for use as a movable power supply connection for cord and plug connected electrical utilization equipment and shall not serve as fixed wiring of a structure or of fixed furnishings, such as but not limited to applications in permanent countertops of kitchens and bathrooms.
1.2 A cord-and-plug-connec
1.3 A cord-and-plug-connec
1.4 A cord-and-plug-connec
1.5 These requirements cover RPT with more than two receptacle outlets that employ a surge protective device (SPD) shall also comply with the applicable requirements for cord-connected, Type 3 Surge Protective Device (SPD) in the Standard for Surge Protective Devices, UL 1449.
1.6 A cord-and-plug-connec
1.7 This standard does not cover RPT including those employing Hospital Grade receptacles or Hospital Grade plugs (see 1), intended for use with medical equipment. RPT are not suitable for use in Category 2 (General Patient Care) Spaces or Category 1 (Critical Patient Care) Spaces or Patient Care Vicinities of health care facilities.
1.8 These requirements do not cover a cord-and plug-connected product, Health Care Facility Receptacle Assemblies (HCOA), covered by the Outline of Investigation for Cord-and-Plug-Connec
1.9 These requirements do not cover a cord-and-plug-connec
1.10 A RPT may employ an integral cord reel for the supply cord and attachment plug. A cord reel provided with pull out receptacle outlets or cord connectors is covered under the Standard for Cord Reels, UL 355.
1.11 These requirements do not cover RPT with work surfaces or surfaces intended to support weight loads other than as specified in 16 for the storage of hand-held electronic devices and charging equipment such as a cell phone, cell phone charger and the like.
1.12 These requirements cover RPT provided with isolated secondary circuits.
1.13 These requirements cover RPT provided with batteries located in isolated secondary circuits. See UL 1363 Annex B - Relocatable Power Taps Incorporating Batteries.
1.14 A product that has a battery backup feature or other uninterruptible power supply equipment located in the Primary Circuit shall comply with the applicable requirements in the Standard for Uninterruptible Power Supply Equipment, UL 1778.
1.15 A RPT with three or more receptacle outlets may employ a Light Emitting Diode (LED) Luminaire.
1.16 A cord-and-plug-connec
1.17 This standard contains the following Annexes:
- a) Annex A - Extendable Relocatable Power Taps.
- b) Annex B - Relocatable Power Taps Incorporating Batteries.
- c) Annex C - Relocatable Power Taps Employing An Integral Thermal Interruption Mechanism.
Document History