ASTM International - ASTM E3474-25

Standard Test Method for Measuring the Air Leakage Rate of the Building Envelope of an Individual Test Zone within a Multizone Building

active
Buy Now
Organization: ASTM International
Publication Date: 1 August 2025
Status: active
Page Count: 6
ICS Code (Thermal insulation of buildings): 91.120.10
significance And Use:

5.1 The ability to accurately measure the airtightness of a portion of a building envelope is significant to diagnostic testing, compliance testing, ventilation and space conditioning load... View More

scope:

1.1 This test method provides a quantitative ?eld test procedure and calculation method for assessing an air leakage rate using fan-induced pressure differentials across the test envelope and the surrounding building, generated by multiple blower doors or equivalent equipment.

1.2 Building setup conditions in accordance with de?ning the test boundaries appropriate for testing air leakage rate through a zone of a building are de?ned in this test method.

1.3 Procedures to determine the air pressure boundaries of the test envelope to be tested are provided in this test method.

1.4 This test method applies to measurement of the building envelope air leakage rate of a zone of a multizone building.

1.5 This test method de?nes three test procedures: multi-point regression, repeated single-point, and repeated two-point air leakage rate testing.

1.6 This test method allows for testing the test envelope in a pressurized condition, a depressurized condition, or in both conditions and averaging the results.

1.7 This test method applies to an air leakage rate test speci?cation with a specified reference pressure greater than 10?Pa (0.04?in. W.C.) and not greater than 100?Pa (0.40?in. W.C.).

1.8 This test method describes two methods of preparation for the building in order to conduct the test: the building envelope where HVAC-related openings are excluded, and the operational envelope where the HVAC-related openings are included.

1.9 Units-The values stated in SI units are to be regarded as standard. The values given in parentheses after SI units are provided for information only and are not considered standard.

1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.

1.11 This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.

Document History

ASTM E3474-25
August 1, 2025
Standard Test Method for Measuring the Air Leakage Rate of the Building Envelope of an Individual Test Zone within a Multizone Building
1.1 This test method provides a quantitative ?eld test procedure and calculation method for assessing an air leakage rate using fan-induced pressure differentials across the test envelope and the...