NG TGN(E) 282
Technical Guidance Notes - Reyrolle Air Blast Circuit Breaker OIBR140 Silencer Dome Installation Procedure
| Organization: | NG |
| Publication Date: | 1 April 2015 |
| Status: | active |
| Page Count: | 4 |
scope:
PURPOSE AND SCOPE
Following the recent failure of OIBR 140 ABCB at Bolney X110, it is considered the 5/8W x4" Cap Head screws used to secure the Silencer Domes are a driving factor in the failure. All cap head screws require to be replaced to remove the requirements detailed within OESB 15/2014.
The following procedure shall be followed to change and tighten the Silencer Dome cap head screws to a set torque.
Torque values as agreed with the manufacturer and endorsed by ERA Technologies LTD and National Grid Network Engineering.