UNLIMITED FREE
ACCESS
TO THE WORLD'S BEST IDEAS

SUBMIT
Already a GlobalSpec user? Log in.

This is embarrasing...

An error occurred while processing the form. Please try again in a few minutes.

Customize Your GlobalSpec Experience

Finish!
Privacy Policy

This is embarrasing...

An error occurred while processing the form. Please try again in a few minutes.

IEEE - P37.20.7/D7

Draft Recommended Practice for Testing Switchgear Rated Up to 52 kV for Internal Arcing Faults

pending
Organization: IEEE
Publication Date: 1 January 2024
Status: pending
Page Count: 105
scope:

This recommended practice establishes methods by which equipment may be tested for resistance to the effects of arcing due to an internal fault. Equipment types covered in this recommended practice include metal-enclosed switchgear as defined by IEEE Std C37.20.1™, IEEE Std C37.20.2™, IEEE Std C37.20.3™ and IEEE Std C37.20.9™; metal-enclosed bus as defined by IEEE Std C37.23™; medium-voltage ac controllers as defined by UL 347; motor control centers as defined by UL 845; switchboards as defined by UL 891; and metal-enclosed medium-voltage air-insulated circuit breakers for outdoor application defined by IEEE Std C37.04™ (see note). This recommended practice applies only to equipment utilizing air or other insulating gas as the primary insulation medium and rated 52 kV ac or below. It applies to both indoor and outdoor equipment; however, special consideration should be given to the building size and construction for indoor applications (not fully addressed by this document).

The tests and assessments described in this recommended practice are only applicable to arcing faults occurring entirely in air within the enclosure when doors and covers are properly secured in accordance with the rated accessibility type. This recommended practice does not apply to arcing faults that occur within components of the equipment, such as instrument transformers, sealed interrupting devices, fuses, and so on.

Designs that meet the requirements of this recommended practice will be referred to as arc-resistant.

NOTE-These circuit breakers are sometimes referred to as dead-tank circuit breakers.3

3 Notes in text, tables, and figures are given for information only and do not contain requirements needed to implement the recommended practice..

Document History

P37.20.7/D7
January 1, 2024
Draft Recommended Practice for Testing Switchgear Rated Up to 52 kV for Internal Arcing Faults
This recommended practice establishes methods by which equipment may be tested for resistance to the effects of arcing due to an internal fault. Equipment types covered in this recommended practice...
March 25, 2021
Testing Switchgear Rated up to 52 kV for Internal Arcing Faults Corrigendum 1
Abstract: A procedure for testing and evaluating the performance of switchgear for internal arcing faults is covered. A method of identifying the capabilities of this equipment is given. Service...
December 6, 2017
Testing Switchgear Rated Up to 52 kV for Internal Arcing Faults
This guide establishes methods by which equipment may be tested for resistance to the effects of arcing due to an internal fault. Equipment types covered in this guide include metal-enclosed...
February 2, 2010
Testing Metal-Enclosed Switchgear Rated up to 38 kV for Internal Arcing Faults Corrigendum 1
This guide establishes a method by which metal-enclosed switchgear, as defined by IEEE Std C37.20.2-1999 and IEEE Std C37.20.3-2001, can be tested for resistance to the effects of arcing due to an...
November 1, 2009
Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults
This guide establishes a method by which metal-enclosed switchgear, as defined by IEEE Std C37.20.2-1999 and IEEE Std C37.20.3-2001, can be tested for resistance to the effects of arcing due to an...
April 16, 2008
Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults
This guide establishes a method by which metal-enclosed switchgear, as defined by IEEE Std C37.20.2-1999 and IEEE Std C37.20.3-2001, can be tested for resistance to the effects of arcing due to an...
September 27, 2007
Testing Metal-Enclosed Switchgear Rated Up to 38 kV for Internal Arcing Faults
This guide establishes a method by which metal-enclosed switchgear, as defined by IEEE Std C37.20.2-1999 and IEEE Std C37.20.3-2001, can be tested for resistance to the effects of arcing due to an...
December 7, 2001
Testing Medium-Voltage Metal-Enclosed Switchgear for Internal Arcing Faults
This guide establishes a method by which metal-enclosed switchgear, as defined by IEEE Std C37.20.2-1999 and IEEE Std C37.20.3-2001, can be tested for resistance to the effects of arcing due to an...

References

Advertisement