NPFC - MIL-G-53133
GENERATOR SETS, SKID MOUNTED, TACTICAL, QUIET, DIESEL ENGINE DRIVEN, ALTERNATING CURRENT 5 THROUGH 60 KILOWATTS, GENERAL SPECIFICATION FOR
| Organization: | NPFC |
| Publication Date: | 30 August 1993 |
| Status: | inactive |
| Page Count: | 51 |
scope:
This specification covers the general requirements for generator sets (hereinafter referred to as "set" or "sets"), skid mounted, tactical, quiet, alternating current, diesel engine driven, 5 through 60 kilowatts.
The sets shall be tactical and of the following modes and sizes:
MODE: I - 50/60 Hz II - 400 Hz III - 60 Hz SIZE: 5 - 5 kW, MODE II and III 10 - 10 kW, MODE II and III 15 - 15 kW, MODE I and II (12.5 kW at 50 Hz) 30 - 30 kW, MODE I and II (25 kW at 50 Hz) 60 - 60 kW, MODE I and II (50 kW at 50 Hz)
Beneficial comments (recommendations, additions, deletions) and any pertinent data which may be of use in improving this document should be addressed to: US Army Belvoir Research, Development, and Engineering Center, ATTN: SATBE-TSE, Fort Belvoir, VA 22060-5606 by using the Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by letter.
The set shall be rated 0.8 power factor (pf), lagging, and shall be re-connectable for the following voltages:
- 5/10 kW, 60 Hz and 400 Hz a. 120-volt, single phase, 2 wire b. 120/240-volt, single phase, 3 wire c. 120/208-volt, 3-phase, 4 wire - 15/30/60 kW, 50/60 Hz and 400 Hz a. 120/208-volt, 3-phase, 4 wire b. 240/416-volt, 3-phase, 4 wire.
This appendix is a mandatory part of the specification. The information contained herein is intended for guidance only. This document clarifies the limits, test methods and general procedures to be used for measurement of EMI on mobile electric power generating sources (MEPGS). Clarification as to the use of MIL-STD-462 is included. This document is intended to be used as a clarifying supplement for the use of MIL-STD-462 and does not replace MIL-STD-462.
The appendix is a mandatory part of the specification. The information contained herein is intended for compliance only.
The appendix is a mandatory part of the specificatin. The information contained herein is intended for compliance only.
The appendix is a mandatory part of the specificatin. The information contained herein is intended for compliance only.
To determine if the tactical quiet generator sets can withstand the effect of solar loading without physical damage or compromises in operational ability.
intended Use:
The sets are intended to supply power for multipurpose use in military applications.